3.4 Module Placement Test
You must test the placement of each wireless device before you permanently mount them. The module
placement test will determine whether the location you have selected is Good, Fair or Bad. If you get a Bad
result, relocate the device and perform the test again. To test each wireless device, perform the following:
1. Enter Installer’s Programming and enter programming section [904].
2. Enter the two digit zone number for the device to be tested
3. Test each device according to their type:
Door Contact. Open and close the contact by moving the magnet or by operating the external device
connected to the contact. The control unit will display the test result after the zone is restored.
Motion Detectors and Smoke Detectors. Remove the Detector from its backplate, wait for 5 seconds,
then reattach the Detector to its backplate. The control unit will display the test result after the Detector is
reattached to its backplate.
4. Verify the results of the test using the following table:
Good ...............Light 1 On Steady ...........1 Beep
Fair ..................Light 2 On Steady........... 2 Beeps
Bad..................Light 3 On Steady...........3 Beeps
5. Continue Steps 3 through 5 until each device has been tested.
Wireless devices can be mounted where results were Good or Fair. No device should be mounted
where a Bad test result was indicated. If multiple tests on the same device are performed you
must wait at least 10 seconds between tests.
WLS908 Panic Pendant Test
The panic pendant cannot be tested in the module placement test, so follow these steps:
1. Begin testing when your system is in the ready state and the Ready light is ON.
2. Press and hold the small middle button on the pendant marked “Test” for two seconds. Once the test is
complete and if the pendant’s battery condition is normal, the Ready light will turn off for four to five
seconds.
3. If the pendant’s battery is low, the Trouble light will turn ON and a series of continuous beeps will be heard.
This test should also be performed by the user when they perform a weekly system test.
If a low battery condition is detected, you must immediately replace the unit. Once you have obtained the new
unit, perform the following:
1. Enter Installer’s Programming and enter programming section [804].
3. Enter the two digit number for the pendant to be replaced.
4. Enter serial number [00000].
5. Enter the two digit number for the pendant being replaced.
6. Enter the serial number of the new pendant. Press [#] twice to exit Installer Programming.
3.5 Supervision
Wireless zones are supervised so that a trouble is generated when a device ceases to operate or is removed
from the system. To enable zone supervision, enter the following:
1. Enter Installer’s Programming and enter programming section [804].
2. Enter section [82] to enable or disable wireless zone supervision (see Section 2.4 “Programming Toggle
(ON/OFF) Option Sections” for how to program these options).
The supervisory option for any WLS908 panic pendants enrolled on the system must be OFF.