1
SPECIFICATIONS
Control Panel Specifications
21 zones including:
16 fully programmable supervised zones (EOL resistors)
Supervised fire zone
1 auxiliary normally open zone
3 keypad activated zones
Audible alarm output:
Bell output
700 mA, fused at 5 Amps, 12 V
DC unregulated
Steady or pulsed output
EEPROM memory:
Does not lose codes or system status on complete AC
and battery failure
Programmable output:
Transistor switch sinks 50 mA to ground
Operation controllable through program options
Powerful 1.5 amp regulated power supply:
400 mA auxiliary supply, 12 V
DC unregulated
Separately fused for battery, keypad/auxiliary supply and
bell output
Supervision for loss of AC power, low battery
Internal clock locked to AC power frequency
Switched Smoke Detector Supply Output:
Controlled from keypad [Q][4] command
Battery required:
12 volt 4 Ah minimum rechargeable gel-cell or sealed
lead-acid battery
Transformer required:
16.5 VAC, 40VA
Dimensions:
11” x 11.8” x 3.3” deep (279 x 300 x 84 mm)
Weight:
6.5 lbs (3 kg)
Remote Keypad Specifications
(PC3000RK)
Four wire (QUAD) hook-up and up to 3 keypads per
system
Built-in piezoelectric buzzer
Full annunciation of zones and system status
Nominal current draw 60 mA
Dimensions 5.5” x 4.5” x 1” deep (140 x 114 x 25 mm)
Output Voltage Specification
Typically, with normal AC in and a fully charged battery, the
output voltage will be 13.8 V
DC. With AC off and a
discharged battery, the voltage will go to 10 volts. Devices
that require power from the control panel should be capable
of normal operation over the voltage range of 10 to 14 V
DC.
Digital Communicator Specifications
94 reporting codes
Transmits all 10BPS and 20BPS single line and extended
formats
Radionics Rounds and Radionics Parity formats
Sescoa Superfast format
3/1, 4/2 and hexadecimal numbers
DTMF and Pulse dialing
DPDT line seizure
True dial tone detection
Anti-jam feature
Two telephone numbers and two account codes
Split reporting of selected transmissions to each
telephone number