MN-220 SERIES - 2 WIRE SMOKE DETECTORS
• RED solid state LED indicator light
• Optional Form 'C' auxiliary relay
• 57°C (135°F) fixed temperature heat sensor option
• Magnet-activated sensitivity test switch
• ULC listed S529 / UL listed UL268
MODELS
MN220 2-wire detector
MN220T 2-wire detector, fixed temp 135°F (57°C) sensor
MN220R 2-wire detector, Form 'C' auxiliary relay
MN220RT 2-wire detector, Form 'C' auxiliary relay,
fixed temp 135°F (57°C) sensor
OPERATION
On alarm, the detector sends an alarm signal to the control panel and activates
the optional auxiliary relay. When the smoke clears from the chamber the detec-
tor and auxiliary relay remain latched in the alarm state until reset by turning off
the power supply for 2 seconds from the control panel.
Detectors with the Temperature Sensor (T) option cannot be reset until the high
heat condition is relieved.
SPECIFICATIONS
Nominal operating voltage..............................12 - 24VDC or VFWR
Maximum operating voltage range ................10 - 30VDC, or 10 - 26.4VFWR
Standby Current
@12V @24V
MN220..........................15 µA 50µA
MN220T........................25µA 60µA
MN220R ......................15µA 50µA
MN220RT ....................25µA 60µA
Alarm Current ..................................................52±2mA @12 & 24 VDC
Electrical compatibility : DSC model MN220 detectors are system fire
detectors. When used in 2-wire operation, the detectors and controls must have
compatibility listing with Underwriters’ Laboratories.
Auxiliary relay rating (resistive)
Form 'C' relay ................................................2A at 30 VDC /VAC
Temp sensor ..................................................135°F (57 °C) fixed
Smoke sensitivity ..........................................2.4%/ft obscuration ±0.5%/ft
2.4%/ 305mm ±0.5% /305mm
Operating environment ................................32 - 122°F (0 - 50 °C)
5% - 95 % RH, non-condensing
Field test ........................................................Magnet-activated switch and/ or
Gemini 501 Smoke Alarm Analyzer
OPERATION
On alarm, the detector sends an alarm signal to the control panel, and activates the
optional sounder and auxiliary relay. When the smoke clears from the chamber, the
sounder stops while the detector and auxiliary relay remain latched in the alarm state
until reset by turning off the power supply for 2 seconds from the control panel.
Detectors with the Temperature Sensor (T) option cannot be reset until the
high heat condition is relieved.
Alarm
Initiating
Circuit
V+
V–
12 to 24 Vdc
EOL
Resistor
End of Line
Device
AUX RelayAUX Relay
+
+
I
NO
C
+
+
I
NO
C
+
+
I
NO
C
C
NC
NO
C
NC
NO
WIRING DIAGRAM
V+
V–
12 to 24 Vdc
End of Line
Device
AUX RelayAUX Relay
++
I
++
I
++
I
NC
NO
C
NC
NO
C
WIRING DIAGRAM
0 102030405060
Alarm Current (mA)
Detector Voltage (VDC)
3
6
9
12
15
18
21
24
27
30
220 SER ES V CURVE
MN-140 SERIES - DC POWERED SMOKE ALARM
• GREEN solid-state LED indicator light
• Loud 85dB piezoelectric alarm sounder
• Interconnect up to 20 detectors
• Removable terminals for easier wiring
• Optional Form 'A' (normally open, alarm closed) and/or Form 'C'
(normally open/normally closed) alarm relays
• 57°C (135°F) fixed temperature heat sensor option
• Test Button for user to perform sensitivity test
• Automatic self-test every 40 seconds with audible trouble indication
if the detector has insufficient smoke sensitivity
• ULC listed S531
MODELS
MN-140 Form 'A' alarm relay, sounder, interconnect
MN-140T As MN-140 plus 57°C (135°F) sensor
MN-140R As MN-140 plus Form 'C' auxiliary relay
MN-140RT As MN-140 with Form 'C' auxiliary relay, 57°C (135°F) sensor
MN-140C Form 'C' alarm relay, sounder, interconnect
MN-140CT As MN-140C plus 57°C (135°F) sensor
MN-140CH As MN-140C plus isolated 57°C (135°F) sensor as
heat detector with Form 'A' relay
WLS906 WIRELESS SMOKE ALARM
• RED solid-state LED indicator light
• Loud 85dB piezoelectric alarm horn
• Uses six AA batteries and special circuit design to provide extra
long battery life
• Battery removal sensor alerts user to missing battery
• Visible flash light and audible trouble chirp for low battery warning
• Automatic self-test once every 40 seconds provides an audible
trouble indication if the unit has insufficient smoke sensitivity
• Test Button allows user to perform sensitivity test and get a local
indication of test result
• Magnet-activated reed-switch allows user to perform system test
• Equipped with an RF transmitter for communication with DSC's
WLS900 Wireless and Power 832 Security Systems
• ULC listed S531, Listed to UL217 and UL268
OPERATION
On alarm, the detector sends an alarm signal to the control panel, and activates
the sounder and optional auxiliary relays. When the smoke clears from the
chamber the detector automatically resets itself.
Detectors with the Temperature Sensor (T) option will not reset until the high
heat condition is relieved.
Interconnected Units
Up to 20 detectors may be interconnected. When one detects smoke or heat, it
and all interconnected "remote" detectors will sound. Units detecting smoke or
heat will activate their alarm and auxiliary relays, and their LEDs will shut OFF.
Detectors not detecting smoke or heat will not activate their relays and their LEDs
will remain ON. This will assist in locating the detector(s) that initiated the alarm.
OPERATION
On alarm, the detector activates the sounder and sends an RF alarm signal
to the control panel. When the smoke clears from the chamber the detector
automatically resets itself.
ALARM INDICATIONS
Condition Sounder Alarm LED RF Transmission
No smoke silent flash every supervision
††
40-50sec
Smoke alarm flash every alarm
0.67sec
Automatic self test silent flash every supervision
††
- functioning normally 40-50sec
Automatic self test chirp between flash every fire trouble
- insufficient sensitivity LED flashes 40-50sec
Push button sensitivity test alarm flash every supervision
††
- functioning normally 0.67sec
Push button sensitivity test silent flash every fire trouble
- insufficient sensitivity 40-50sec
Magnet sensitivity test alarm flash every alarm
- functioning normally 0.67sec
Magnet sensitivity test silent flash every fire trouble
- insufficient sensitivity 40-50sec
Low battery chirp simultaneous flash every fire trouble
with LED flash 40-50 sec
††
transmits every 12 minutes
Operating environment ..............................32 - 122°F (0 - 50 °C)
5% - 95 % RH, non-condensing
Field test ....................................................Pushbutton and/or
Gemini 501 Smoke Alarm Analyzer
V+
V–
12 to 24 Vdc
To
Interconnected
Units
To
Interconnected
Units
NC
COM
I/O
NO
NC
COM
I/O
NO
I/O
NU
+
I
NO
COM
+
I
NO
COM
+
I
WIRING DIAGRAM
MN-240 SERIES - 4 WIRE SMOKE DETECTORS
• RED solid state LED indicator light
• Form 'A' (normally opened, alarm closed) alarm relay (standard);
optional Form 'C' (normally opened/normally closed) auxiliary relay
• 57°C (135°F) fixed temperature heat sensor option
• Optional Loud 85dB piezoelectric alarm sounder
• Audible trouble indication (in sounder-equipped units) if the unit
has insufficient smoke sensitivity
• ULC listed S529 / UL listed UL 268
MODELS
MN240 Form 'A' alarm relay
MN240T Form 'A' alarm relay, fixed temp 135°F (57°C) sensor
MN240R Form 'A' alarm relay, Form 'C' auxiliary relay
MN240RT Form 'A' alarm relay, Form 'C' auxiliary relay,
fixed temp 135°F (57°C) sensor
MN240S Form 'A' alarm relay, sounder
MN240ST Form 'A' alarm relay, sounder, fixed temp 135°F (57°C) sensor
MN240SR Form 'A' alarm relay, sounder, Form 'C' auxiliary relay
MN240SRT Form 'A' alarm relay, sounder, Form 'C' auxiliary relay,
fixed temp 135°F (57°C) sensor
SPECIFICATIONS
Nominal operating voltage..............................12 - 24VDC or VFWR
Maximum operating voltage range ................10 - 30VDC, or 10 - 26.4VFWR
Standby Current Alarm Current
@12V @24V @12V & 24V
MN240..........................15 µA 45µA 35mA
MN240T ........................25µA 60µA 35mA
MN240R ......................15µA 45µA 60mA
MN240RT......................25µA 60µA 60mA
MN240S........................15µA 45µA 45 mA
MN240ST......................25µA 60µA 45mA
MN240SR ....................15µA 45µA 70mA
MN240SRT ..................25µA 60µA 70mA
Relay rating (resistive)
Form 'A' relay ..................................................1A at 30VDC /VAC
Form 'C' relay ..................................................2A at 30VDC /VAC
Temp sensor ..................................................135°F (57°C) fixed
Smoke sensitivity ........................................2.4%/ft obscuration ±0.5%/ft
2.4%/ 305mm ±0.5% /305mm
Operating environment ................................32 - 122°F (0 - 50°C)
5% - 95 % RH, non-condensing
Field test ......................................................Magnet-activated switch and/or
Gemini 501 Smoke Alarm Analyzer
SPECIFICATIONS
Nominal operating voltage ........................12 - 24 VDC or VFWR
Maximum operating voltage range ............10 - 30VDC, or 10 - 26.4VFWR
Standby current ..........................................17mA
Alarm Current
MN140(T) ....................................................40mA maximum
MN140C(T) ................................................45mA maximum
MN140R(T) ................................................65mA maximum
MN140CH ....................................................65mA maximum
Relay rating (resistive)
Form 'A' relay ..............................................1A at 30V
DC /VAC
Form 'C' relay ..............................................2A at 30VDC /VAC
Temp sensor ..............................................135°F (57 °C) fixed
Smoke sensitivity ......................................2.5%/ ft obscuration ±0.5%/ft
2.5% /305mm ±0.5 %/305mm
SPECIFICATIONS
Operating voltage ........................9V (six AA alkaline batteries)
Smoke sensitivity ........................2.4%/ ft obscuration ±0.5%/ft
2.4% /305mm ±0.5 %/305mm
Operating environment ..............32 - 122°F (0 - 50°C)
5% - 95 % RH, non-condensing
Field test ....................................Pushbutton, magnet-activated reed switch
and/or Gemini 501 Smoke Alarm Analyzer