
21
Notes: The maximum delays allowed for UL
residential installations are: Entry delay = 45 seconds;
Exit delay = 60 seconds.
The maximum delays allowed for UL commercial
installations are: Entry delay = 60 seconds; Exit delay
= 60 seconds.
In UL commercial installations the bell cut-off time
shall be a minimum of 15 minutes.
[21] Auxiliary Delay Zone Times
This section requires 2 three digit entries to establish the
auxiliary entry and exit delay times. Do not press the [#] key
during data entry. The entry default time is 45 seconds and
may be changed to any time from ‘001’ second to ‘255’
seconds. The exit default time is 60 seconds and may be
changed to any time from ‘001’ second to ‘255’ seconds.
For the auxiliary delay times to be effective on a zone,
the zone must be set as type [7] in section [14] Zone
Definitions.
Note: The maximum delays for UL residential
installations are: Entry delay = 45 seconds Exit delay =
60 seconds.
For UL installations, swinger shutdown cannot be
enabled. Each alarm must be transmitted. As well, the
delay before transmission must not exceed 15 seconds.
[22] Communication Variables
Once this section is entered, 2 two digit numbers are
expected. Do not press the [#] key while entering data.
The first two digit number defines the number of alarm and
restoral pairs per zone that the communicator will make
before it shuts down for that zone. (Swinger shutdown).
The system will still go into a local alarm (Bell or siren)
unless section [18] light 8 is on to make the bell follow the
swinger shutdown counter. The counter may be reset
either when the panel is armed or on a 24 hour basis as
defined in the 3rd system option code, zone light 7. The
number of alarms may be programmed from ‘00’ to ‘99’
where ‘00’ means the communicator will never shutdown.
The fire zone cannot be shutdown, it always transmits.
The second two digit number defines the delay before
transmission. This delay is for zones defined as burglary
zones only. 24 hour zones or the fire zone will not be
delayed. The time may be programmed from ‘00’ to ‘99’
seconds where ‘00’ means no delay. If the system is
disarmed before the transmission delay expires, then no
transmission will take place.
[23] System Clock Times
After the section number [23] is entered, three 4 digit
numbers are expected. These numbers are the following
system times:
• Automatic arming time of day (HH:MM)
• For future use (99:99)
• Test transmission time of day (HH:MM)
Times are entered using the “24 hour clock” (military time).
Valid entries are 00 to 23 for HH (i.e. hours) and 00 to 59
for MM (i.e. minutes).
Note: IF INVALID TIMES ARE
ENTERED FUNCTIONS WILL NOT WORK. The
automatic arm function is enabled and disabled using
the [
✱
]+[6]+[Master Code] User’s Function Commands.
Auto-arm cannot be used for UL installations.
Light on= Keypad no buzzer on panic alarm
(See Keypad Zones.)
[7]*Light off= The [F]ire key is enabled
Light on= The [F]ire key is disabled
[8]*Light off= Disable bell shutdown
Light on= Enable bell shutdown
The bell will follow the swinger shutdown counter as set
in section [22].
* is default condition
[19] Zones 1 to 8 Bypass Mask
Use the same method of programming as used in section
[15]. Using this section it is possible to control which zones
the user is able to bypass using the [✱][1] command. If the
zone light is on the zone can be bypassed. If the zone light
is off that zone cannot be bypassed.
[20] System Times
Once the section number is entered, 6 two digit numbers
are expected to be entered. The valid range for entries in
this section is 01 to 99. Hex values or 00 are not allowed.
The times are entered in the following order:
• Entry delay time (in seconds)
• Exit delay time (in seconds)
• Bell cut-off time (in minutes)
• Delay before AC failure trouble reporting (in minutes)
• Slow zone response time (in 10 ms increments)
• Default zone response - 500 ms
• Test transmission/periodic download cycle time (in
days)
AC Failure Reporting Code is transmitted after the delay
programmed, which may be up to 99 minutes. The
reporting code for AC Failure Trouble is programmed in
sections [12] and [13].
The Zone Response Time is the length of time that an
alarm condition must be present on a zone before it is
detected. Certain vibration detectors, shock sensors and
glass break detectors require a fast response zone in
order to operate. The zones to which these types of
detectors are connected should be programmed as fast
response zones. All other zones should be programmed
as slow response zones. Zones are defined as either fast
or slow response time in section [14]. The fast response
time is fixed at 20 ms. The Slow Zone Response Time is
programmable in increments of 10 ms. The normal entry
would be 50 for a 500 ms slow response time.
A Test Transmission or a Periodic Download is sent to
the monitoring station on a regular basis to confirm that the
communication link to the system is intact. The test
transmission/periodic download cycle time is how often (in
days) the test transmission and /or periodic download is
sent. The reporting code for the test transmission is
programmed in section [12]. The time of day that the test
transmission and/or periodic download is sent is
programmed in section [23].
To enable either option, lights 7 and 8 in section [48]
must be programmed. If both test transmission and
periodic download are enabled, the same time will be
used for both. The test transmission will transmit first and
after it goes off line a periodic download will take place.
Commentaires sur ces manuels