
4
Programmable Output Terminals – PGM1 and PGM2
PGM1 can sink up to 50mA or
300mA (depending on the PGM
build option) of current. Connect the
positive side of the LED or buzzer to
AUX+, the negative side to PGM1. If
more than 50mA or 300mA of current
are required, a relay must be used.
PGM2 operates similarly to PGM1.
However, both PGM1 and PGM2 can
not sink up to 300mA of current. If
PGM1 or PGM2 is built to sink
300mA of current the other PGM out-
put will be built to sink 50mA of cur-
rent, please see "Programmable Outputs" in section 1.1
"Specifications". Please study PGM wiring in the above dia-
gram. For a list of the programmable output options, please
see section 5.11 "PGM Output Options".
Zone Input Terminals – Z1 to Z4
Each detection device must be connected to a zone on the
control panel. We suggest that one detection device be con-
nected to each zone; wiring multiple detection devices to a
single zone, however, is possible. For zone wiring specifics,
please see section 2.8 “Zone Wiring”.
Telephone Connection Terminals – TIP, RING, T-1, R-1
If a telephone line is required for central station communica-
tion or downloading, connect an RJ-31X telephone jack in the
following manner:
NOTE: Please ensure that all plugs and jacks meet the dimen-
sion, tolerance and metallic plating requirements of 47 C.F.R.
Part 68, SubPart F. For proper operation, no other telephone
equipment should be connected between the control panel and
the telephone company facilities. Do not connect the alarm
panel communicator to telephone lines intended for use with a
fax machine. These lines may incorporate a voice filter which
disconnects the line if anything other than fax signals are
detected, resulting in incomplete transmissions.
2.3 Keybus Operation and Wiring
The Keybus is used by the panel to communicate with all con-
nected modules and vice versa. The red (AUX+) and black
(AUX-) terminals are used to provide power, while the yellow
(YEL) and green (GRN) terminals are clock and data respec-
tively.
NOTE: The four Keybus terminals of the panel must be con-
nected to the four Keybus terminals or wires of all modules.
The following restrictions apply to Keybus wiring:
• Keybus should be run in minimum 22 gauge quad
(0.5mm); two pair twist is preferred.
• The modules should be home-run to the panel but can be
connected in series or T-tapped.
• Any module can be connected anywhere along the Key-
bus. You do not need to run a separate Keybus wire for
keypads, etc.
• No module can be more than 1,000'/305m (in wire length)
from the panel.
• Shielded wire should not be used.
Example of Keybus Wiring
NOTE:
Module (A) is correctly wired
within 1,000'/305m of wire
from the panel.
Module (B) is correctly wired
within 1,000'/305m of wire
from the panel.
Module (C) is NOT wired cor-
rectly as it is further than 1,000'/305m from the panel, in wire
distance.
2.4 Current Ratings – Modules & Accessories
In order for the PC585 system to operate properly, the power
output capabilities of the main control and the expansion
devices must not be exceeded. Use the data presented below
to ensure that no part of the system is overloaded and cannot
function properly.
PC585 (12 V
DC)
AUX+: ........550mA: Subtract the listed rating for each key-
pad, expansion module and accessory con-
nected to AUX+ or Keybus.
BELL: .........700mA continuous rating; 3.0A short term. Avail-
able only with standby battery connected.
PC585 Device Ratings (at 12 V
DC)
• LCD5500Z keypad: 85mA
• LCD5501Z keypad: 90mA
• LCD5501Z32-433 keypad receiver: 260mA
• PC1555RKZ keypad: 85mA
• PC5502Z2 keypad: 25mA
• PC5508Z keypad: 80mA
• PC5516Z keypad: 90mA
• PC5532Z keypad: 120mA
• PC5400 serial module: 65mA
• PC5132 wireless receiver: 125mA
Other Devices
Please read the manufacturer’s literature carefully to deter-
mine the maximum current requirements for each device—
during activation or alarm—and include the proper values for
loading calculations. Connected devices must not exceed
system capabilities during any possible operational mode.
Commentaires sur ces manuels