2
2.1 Overview
Maximum System Capabilities
• Control Unit - 1 PC6010 Main Board
• Up to 256 zones
PC6010 Main Board: 16 zones
PC6108A Expansion Modules: 8 zones each
• 2 Main Board Programmable Outputs (PGM1 & PGM2)
• 1 12 VDC Switched Programmable Auxiliary Power Supply
(Main Board)
• 1 Supervised Programmable Bell/Siren Output (Main Board)
• Up to 64 High Current Programmable Outputs with 16
PC6204 Modules
• Up to 144 Low Current Programmable Outputs with 9
PC6216 Modules
• 1 Serial (Printer) Interface - PC6400
• Up to 16 LCD Keypads - PC6501
• 1 Telephone Interface (Main Board)
• 1 Backbone Interface (using PC6442, PC6443 Modules)
User Interface
• Simple menu structure based on questions, displayed on
PC6501 LCD keypad.
• Four user types available: Basic, Advanced, Supervisor, and
Master
• The menu the user sees is limited to the functions allowed to
their user type
• Utility functions are available to users, such as remote control
doorstrikes and resetting smoke detectors.
256 Programmable Zones
• 16 zones on the main board
• Expand the system to 256 zones using PC6108A expansion
modules
• 19 zone types, including:
• Standard Delay • Auto Verify Fire
• Force Arm Delay • Momentary Arm
• Auxiliary Delay • Maintained Arm
• Instant • 24 Hr Holdup
• Interior • Auxiliary
• 24 Hr Bell • 24 Hr Auxiliary
• 24 Hr Bell/Buzz • 24 Hr Medical
• 24 Hr Buzzer • Seismic
• Standard Fire • LINKS Supervisory
• LINKS Answer
• Zones can be assigned independently to any area, and to any
alarm or seismic group.
Section 2: System Overview
32 Areas
• Separate or shared zones from other areas
• Individual keypads per area
• Individual access codes for each area
• Individual outputs programmable per area
LCD Keypads (PC6501/6501T)
• Total of 16 on the system
• Can be assigned to any area
• User-friendly interface allows fast and simple access to the
system
Access Control (PC6820)
• 16 modules in total - 2 doors per module
• 32 doors total
• Can be used to arm/disarm areas
210 Programmable Outputs
• 2 programmable outputs on the main control panel
• Main board outputs switch to 12VDC, up to 50mA maximum
current draw
• 64 programmable relay outputs - using up to 16 PC6204
Modules
• 144 programmable switched transistor outputs - using up to
9 PC6216 Modules
• Each output can be programmed for 1 of 56 PGM output
options
Switched Auxiliary Output
• Can be programmed for 1 of 56 PGM output options
• 11.6 - 12.6 VDC, 300 mA maximum
Supervised Alarm Output
• Bell Output, 200 mA fused at 5 Amps, 13.8 VDC
• Steady or Pulsed Output
• Can be programmed for 1 of 56 PGM output options
Event Buffer
• Up to 3000 events can be stored in the event buffer
• Each event is logged with a date and time stamp
• System and area events are logged in the event buffer. Area
events are identified by the area label. System events are
identified by the message “System Area”.
• Event Buffer Viewing - Supervisor and Master users can view
2500 events through the keypad, including the date and time
stamp
• Event Buffer Printing - the entire event buffer (3000 events)
can be printed through the Installer’s mode
Internal Memory
• Retains programmed data and system status, even when both
AC and battery have been removed.
• If the panel loses power (indicated by an audible fault beep),
the clock will need to be reset.