
41
Zone Definition SIA Auto Rep
Codes**
Delay, Instant, Interior, Delay
Stay/Away, Interior Stay/Away,
24-hr Burg.
BA-ZZ/BH-ZZ
Standard 24-hr Fire, Delayed 24-
hr Fire
FA-ZZ/FH-ZZ
24-hr Supervisory US-ZZ/UR-ZZ
24-hr Supervisory Buzzer UA-ZZ/UH-ZZ
24-hr Sprinkler SA-ZZ/SH-ZZ
24-hr Gas GA-ZZ/GH-ZZ
24-hr Heat KA-ZZ/KH-ZZ
24-hr Medical MA-ZZ/MH-ZZ
24-hr Emergency (non-medical) QA-ZZ/QH-ZZ
24-hr Waterflow WA-ZZ/WH-ZZ
24-hr Freeze ZA-ZZ/ZH-ZZ
24-hr Holdup HA-ZZ/HH-ZZ
24-hr Panic PA-ZZ/PH-ZZ
Latching 24-hr BA-ZZ/BH-ZZ
** ZZ = zones 01-32
UL Listed Commercial and Residential Installations
The installation requirements listed below must be met for the following grades of service.
Grade A Local
The installation must have a bell UL Listed for mecantile local
alarms (AMSECO MBL10B with model AB-12 bell housing).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(DSC Model CMC-1, P/PC4050CAR, P/PC4004C).
Grade B Central Station and Police Connect
The installation must have a bell UL Listed for mecantile local
alarms (AMSECO MBL10B with model AB-12 bell housing).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(DSC Model CMC-1, P/PC4050CAR, P/PC4004C).
Grade C Central Station
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(DSC Model CMC-1, P/PC4050CAR, P/PC4004C).
All Commercial Installations
• The entry delay must not exceed 60 seconds
• The exit delay must not exceed 60 seconds.
• The minimum bell cutoff time is 15 minutes.
• Quick Exit must be disabled.
• Bell Squawk on Trouble must be enabled.
• Minimum dialing attempts is 5, maximum is 10.
Residential Installations
• The entry delay must not exceed 45 seconds
• The exit delay must not exceed 60 seconds.
• The minimum bell cutoff time is 4 minutes.
• Quick Exit must be disabled.
Programming
The notes in the programming sections describing the system
configurations for UL Listed installations must be implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected area is to be
under the responsibility of one ownership and management (i.e.
one business under one name). This may be a group of buildings
attached or unattached with different addresses but under the
responsibility of someone having mutual interest. The person of
mutual interest is not the alarm installing company.
Bell Location
The alarm sounding device (bell) must be located where it can
be heard by the person or persons responsible for maintaining
the security system during the daily arming cycle.
Protection of the Control Unit
The local control and the local power supply must be protected
by one of the following ways:
• The control unit and audible alarm device must be in a
protected area which is armed 24 hours a day.
• Each partition shall arm the area protecting the control unit
and the audible alarm device power supply. This may
require duplicate protection armed by each partition. Access
to this protected area, without causing an alarm, will require
that all partitions be disarmed.
In all cases described above, the protected area for the control
unit must be programmed as not bypassable.
Casual Users
The installer should caution the user(s) to not give system
information to casual users (e.g. codes, bypass methods, etc.
to baby-sitters or service people). Only the One-Time Use
codes should be given to casual users.
User Information
The installer should advise the users and note in the user
instruction manual:
• Service organization name and telephone number
• The programmed exit time
• The programmed entry time
Zone Reporting Codes
APPENDIXV B
Table B-2: Contact ID Zone Alarm/Restoral Event Codes
(as per ADEMCO):
Program any of these codes for zone alarms/restorals when
using the standard (non-automatic) Contact ID reporting format.
Table B-1 Zone Alarm/Restoral Reporting Codes
For notes on Contact ID or SIA formats, see Appendix A.
Medical Alarms
(1)AA Medical
(1)A1 Pendant Transmitter
(1)A2 Fail to Report In
Fire AlarmsFire Alarms
Fire AlarmsFire Alarms
Fire Alarms
(1)1A Fire Alarm
(1)11 Smoke
(1)12 Combustion
(1)13 Water Flow
(1)14 Heat
(1)15 Pull Station
(1)16 Duct
(1)17 Flame
(1)18 Near Alarm
Panic Alarms
(1)2A Panic
(1)21 Duress
(1)22 Silent
(1)23 Audible
Burglar Alarms
(1)3A Burglary
(1)31 Perimeter
(1)32 Interior
(1)33 24 Hour
(1)34 Entry / Exit
(1)35 Day / Night
(1)36 Outdoor
(1)37 Tamper
(1)38 Near Alarm
General Alarms
(1)4A General Alarm
(1)43 Exp. module failure
(1)44 Sensor tamper
(1)45 Module Tamper
24 Hour Non-Burglary
(1)5A 24 Hour non-Burg
(1)51 Gas detected
(1)52 Refrigeration
(1)53 Loss of Heat
(1)54 Water Leakage
(1)55 Foil Break
(1)56 Day Trouble
(1)57 Low bottled Gas level
(1)58 High Temp
(1)59 Low Temp
(1)61 Loss of Air Flow
Commentaires sur ces manuels