
4
Section 2: Installation and Wiring
The following sections provide a complete description of how to wire and configure devices and zones.
2.1 Installation Steps
The following steps are provided to assist with the installation of the
panel. It is suggested that you read over this section briefly to get an
overall understanding of the order of installation. Once this is done
carefully work through each step. Working from this plan will help
reduce problems and reduce the overall installation time required.
Step 1 Create a Layout
Draw a rough sketch of the building and include all alarm detection
devices, zone expanders, keypads and all other modules that are
required.
Step 2 Mounting the Panel
Locate the panel in a dry area, preferably located near an unswitched
AC power source and the incoming telephone line. Before attaching
the cabinet to the wall be sure to press the five circuit board mount-
ing studs into the cabinet from the back.
NOTE: Complete all wiring before applying AC or connecting the
battery.
Step 3 Wiring the Keybus (Section 2.4)
Wire the Keybus to each of the modules following the guidelines
provided.
Step 4 Assigning Zones to Zone Expanders (Section 2.6)
If zone expander modules are being used the modules must be con-
figured so the panel knows which zones are assigned to each
expander. Follow the guideline provided to assign zones to expanders.
Step 5 Zone Wiring (Section 2.10)
Power down the control panel and complete all zone wiring. Follow
the guidelines provided in section 2.10 to connect zones using nor-
mally closed loops, single EOL resistor, double EOL resistors, Fire
zones and Keyswitch Arming zones.
Step 6 Completing Wiring
Complete all other wiring including bells or sirens, telephone line
connections, ground connections or any other wiring necessary. Fol-
low the guidelines provided in section 2.2 “Terminal Descriptions”.
Step 7 Power up the Control Panel
Once all zone wiring and Keybus wiring is complete, power up the
control panel.
NOTE: The panel will not power up if only the battery is connected.
Step 8 Keypad Assignment (Section 2.7)
Keypads must be assigned to different slots to be properly super-
vised. Follow the guideline provided in section 2.7 to assign keypads.
Step 9 Confirming Module Supervision (Section 2.8)
By default, all modules are supervised upon installation. Supervision
is enabled at all times so that the panel can indicate a trouble if a
module is removed from the system.
To confirm that each module is properly supervised, follow the
guidelines provided in section 2.8.
Step 10Programming the System (Sections 4 and 5)
Section 4.0 provides a complete description of how to program the
panel. Section 5.0 contains complete descriptions of the various pro-
grammable features, what options are available and how the options
function. The Programming Work Sheets should be filled out com-
pletely before attempting to program the system.
Step 11Testing the System
Test the panel completely to ensure that all features and functions
are operating as programmed.
2.2 Terminal Descriptions
NOTE: AC Terminals - AC
The panel requires a 16.5 volt, 40 VA transformer. Connect the trans-
former to an unswitched AC source and connect the transformer to
these terminals.
NOTE: Do not connect the transformer until all other wiring is
complete.
Battery Connection
The battery is used to provide back up power in the event of an AC
power failure and to provide additional current when the panel
demands exceed the power output of the transformer, such as when
the panel is in alarm.
NOTE: Do not connect the battery until all other wiring is com-
plete.
Connect the RED battery lead to the positive of the battery, the
BLACK battery lead to the negative.
Auxiliary Power Terminals - AUX+ and GND
These terminals provide up to 420mA of current at 12 VDC (rated
11.6-12.6 V
DC for UL residential applications) for devices requir-
ing power. Connect the positive side of any device requiring power
to the AUX+ terminal, the negative side to GND. The AUX output is
protected; if too much current is drawn from these terminals (wiring
short) the panel will temporarily shut off the output, until the prob-
lem is corrected.
Bell Output Terminals - BELL+ and BELL-
These terminals provide up to 3 Amps of current at 12 VDC (with
stand-by battery; 700 mA continuous) for powering bells, sirens,
strobes or other warning type equipment. Connect the positive side
of any alarm warning device to BELL+, the negative side to BELL–.
The BELL output is protected; if too much current is drawn from
these terminals (wiring short) the BELL PTC will open.
The Bell output is supervised. If no alarm warning device is being
used connect a 1K
Ω resistor across BELL+ and BELL– to prevent the
panel from displaying a trouble condition (see section [*][2] Trouble
Display on page 11).
Keybus Terminals - RED, BLK, YEL, GRN
The Keybus is used by the panel to communicate with modules and
by modules to communicate with the panel. Each module has four
Keybus terminals that must be connected to the four Keybus termi-
nals on the panel. For more information, see section 2.4 Keybus
Operation and Wiring on page 5.
Programmable Outputs - PGM1, PGM2, PGM3, PGM4
Each PGM output is designed so that
when activated by the panel, the terminal
will switch to ground
PGM1, PGM3, and PGM4 can each sink
up to 50 mA of current. These PGMs can
be used to activate LEDs or a small
buzzer. Connect the positive side of the
LED or buzzer to AUX+, the negative side
to the PGM.
PGM2 is a high current output (300mA)
and operates similarly to PGM1. If more
than 300 mA of current is required, a relay
must be used. Refer to the diagram.
Zone Input Terminals - Z1 to Z8
Each detection device must be connected to a zone on the control
panel. It is suggested that each zone have one detection device how-
ever it is possible to wire multiple detection devices to the same zone.
For zone wiring specifics, see section 2.10 Zone Wiring on page 7.
WWW.DIYALARMFORUM.COM
Commentaires sur ces manuels